Web tension measuring amplifier CV 2201
Make earth and ground connections as shown in the wiring dia-
grams. See also EMC leaflet.
6. Commissioning
6.1 Measuring roller
NOTICE
The measuring rollers must be mounted free of mechanical stress and
move freely.
6.2 Safety barriers
R 40
NOTICE
In conjunction with safety barriers, the bridge voltage UB must be ad-
justed from 10 V DC to the maximum using the potentiometer R40
(right stop).
BEA--250059-EN-03
U 5/12
Free Datasheet http://www.datasheet4u.com/
9.1 Outputs
Web tension measuring amplifier CV 2201
The web tension is available in three different signals:
– Filter output UFilter (0 to ±10 V/10 mA, rise time 2 s) for
instruments.
– Direct output UDirect (0 to ±10 V/10 mA, rise time 5 ms) for fast
measured value acquisition and for downstream control circuits.
– Current output IDirect (0 to 20 mA or 4 to 20 mA, rise time 5 ms) for
measured value transmission over longer distances.
Sliding switch in position 1: 4 to 20 mA
Sliding switch in position 2: 0 to 20 mA (works setting)
NOTICE
Make sure that the load (current sensing resistor) does not exceed a
value of 600 Ohm!
The current output is only active with a positive voltage on the amplifi-
er's input.
Should the load cell output a negative signal voltage, the connections
for the bridge supply voltage +UB and -UB are to be swapped.
BEA--250059-EN-03
U 11/12